Boilers / Burners
Inhaltsverzeichnis
Introduction
In a boiler the chemical energy is converted to thermal energy. The main part of a boiler is the fire box with a burner located inside. All around the fire box pipes or box sections are installed, in which a liquid (mostly water) is heated up by the thermal energy of the combustion.
There are two ways for categorising of boilers:
- by the kind of fuel which is used for the combustion
- (main groups: natural gas, oil, wood, biomass, other combustible materials: for example waste gases in chemical industry)
- or
- by the product as heated water or steam.
The production of heat or steam in boilers is the eldest and best known utilisation of CMM, whereas special burners use CMM as fuel. These CMM burners are also used in some other applications like coal dryer, ventilation air heater or as industrial heaters. For using CMM as a fuel in boilers gases with a wide range of concentration can be utilised. Safe operating systems for methane contents from 25% up to 100 % are available. On some locations utilisation of gases with methane concentration down to 20% are allowed.
CMM as additional fuel
Especially in coal fired power plants with CMM production nearby, CMM can be used as additional fuel in boilers. As the energy amount of the used CMM is small compared to the coal consumption, no special regulation is needed for the burning of the CMM in the big fire box. The safety installations depend on the local situation. In most cases a special regulation of combustion air flow is not required.
However, even if the co-firing of CMM is a simple possibility for CMM utilisation it is only reasonable, if the distance between the CMM extracting point and the power plant is acceptable.
CMM as mono fuel
In the past 20 years CMM has been used as mono fuel in boilers. Special safe burner systems are used instead of natural gas burners in gas boilers. Furthermore there are burners available for use of CMM as normal fuel and oil as secondary fuel. Sometimes a modification for fuel switch is not necessary. This kind of burners and boilers are often used on coal mine sites in Germany.
In many mines especially in Eastern countries coal fired boilers are retrofitted with a gas burner system. The grate is covered to protect it against the flame heat. In most cases a modification of the air inlet is not necessary.
Gas - Air - Mixture in CMM burners =
Precise control and regulation of gas – air – mixture in CMM burners is necessary to ensure complete gas combustion, as well as a low CO content in the exhausted gas and a good efficiency of the overall system.
The burner load is regulated by the energy demand. However, the capacity of gas consumption is limited to the maximum gas volume, which can be charged to the burner. The different CMM qualities (CH4-content) make specific demands on the control and regulation system. For example: If the content CH4 of the CMM can range between 25 % and 60 %, the cross sectional area of the gas flow channel has to be dimensioned for gas with 25% CH4 to reach full load. When the same volume of CMM with 60% CH4 flows through this channel, the load would reach values of 240% as the gas contains more than the double energy compared to the CMM with lower CH4 contents. Therefore maximum volume flow of CMM with 60 % CH4 has to be limited to 42% of the maximum possible volume flow for security reasons.
The proper function of the adjustment of gas and air is controlled through the measurement of oxygen concentration in the exhaust gas, which should be between 1.5% to 3 % at every time.